Casa ProdutosInstrumento de Teste Elétrico

25KVA Primary Current Injection Test Kit High Current Generator Instrument

25KVA Primary Current Injection Test Kit High Current Generator Instrument

    • 25KVA Primary Current Injection Test Kit High Current Generator Instrument
    • 25KVA Primary Current Injection Test Kit High Current Generator Instrument
    • 25KVA Primary Current Injection Test Kit High Current Generator Instrument
  • 25KVA Primary Current Injection Test Kit High Current Generator Instrument

    Detalhes do produto:

    Lugar de origem: CHINA
    Marca: AI
    Certificação: ISO
    Número do modelo: PCI-2

    Condições de Pagamento e Envio:

    Quantidade de ordem mínima: 1 conjunto
    Preço: Negociável
    Detalhes da embalagem: Caixa
    Tempo de entrega: 15 dias
    Termos de pagamento: T/T, Western Union, L/C
    Habilidade da fonte: 100000 conjuntos por mês
    contacto
    Descrição de produto detalhada
    Fonte de energia: AC220V ou AC 400V, 45Hz~65Hz Mostrar: Digital
    palavra-chave: Kit de teste de injeção de corrente primária Corrente de saída: 500A~25KVA
    Capacidade de saída: 3KVA-15KVA Garantia: 1 ano

     

    Primary Current Injection Tester System with Circuit Breaker Timer

    25KVA Primary Current Injection Test Kit High Current Generator Instrument

     

    I. Introduction:

    PCI series primary current injection tester is applied in power system for circuit breaker test, protection system test and current transformer test. The current injection test set generates a high current from power supply to simulate the rated current or fault current in the primary circuit of power equipment.

    The 1000A/15KVA primary injection test system is designed in integrated model.

     

     

    Features:

    1 High current output injected to the main circuit of power line to simulate the fault current. Then check whether the protection system will be operated according to the design.
    2 High current output injected to the primary of current transformer and then measure the inducted current from secondary
    by error measurement instrument to check the ratio error and phase displacement of CT.
    3 High current output injected to the main circuit of circuit breaker to simulate the rated current in primary. Then check the stability of circuit breaker according to the temperature rise procedure.

    4 This primary current injection test set is also considered as a AC high current source in power equipment or cable test.

    5.Current is measured from the secondary of current transformer which is installed in the internal of the current booster.

     

     

    III. Specifications:

    1 Power supply AC220V or AC 400V, 45Hz~65Hz. The power supply voltage is depends on the power output capacity, as below.
    2 Typical output current

    500A or 1000A or 2000A

    Typical output capacity 3KVA or 5KVA or10KVA or15KVA
    It can be customized according to your requirements from above specs

    3 Impendence voltage 8%
    4 Idle current 6%
    5 Current distortion <5%
    6 Display unit 4 and 1/2 digitals current meter
    7 Maximum measurement error 0.5%RDG+5D
    8 Optional timer 1)4 digital timer from 0~9999s / 0~999.9s /0~99.99s, accuracy 0.5%RDG+5D
    2)5 digital timer from 0~99999s / 0~9999.9s /0~999.99s, accuracy 0.2%RDG+2D
    3)6 digital timer from 0~999999s / 0~99999.9s /0~9999.99s, accuracy 0.1%RDG+1D
    9 Work temperature 0~40 C, Humidity <90%

     

     

    Photo of 25KVA/2500A Primary Current Injection Test System

    25KVA Primary Current Injection Test Kit High Current Generator Instrument